IEEE C37.112-2018 Inverse-Time Equations:
━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━
t = TD × (A / (M^p - 1) + B)
Where:
t = Operating time (seconds)
TD = Time dial setting
M = Multiple of pickup (I/Ipickup)
A, B, p = Curve constants
IEEE Curve Constants:
━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━
Moderately Inverse (MI): A=0.0515, B=0.114, p=0.02
Very Inverse (VI): A=19.61, B=0.491, p=2.0
Extremely Inverse (EI): A=28.2, B=0.1217, p=2.0
Short-Time Inverse (SI): A=0.00262, B=0.00342,p=0.02
Long-Time Inverse (LTI): A=5.95, B=0.180, p=2.0
Long-Time EI (LTEI): A=5.67, B=0.352, p=2.0
IEC 60255 Curve Constants:
━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━━
Standard Inverse (A): A=0.14, B=0, p=0.02
Very Inverse (B): A=13.5, B=0, p=1.0
Extremely Inverse (C): A=80, B=0, p=2.0