Out-of-Phase Closing Engineering Calculator
Calculate electrical and mechanical stresses from out-of-phase breaker closure
1
System Parameters Input
Define system base, impedances, and closure conditions
Nominal ±10%: 124.2 – 151.8 kV
Nominal ±10%: 124.2 – 151.8 kV
30°
Optional Inputs (for mechanical stress calculations)
For shaft torque analysis per IEEE C50.13
For winding force & thermal analysis
2
Results Dashboard
Calculated stresses from out-of-phase closure
Voltage Analysis
Vbus (line-to-line)
--
Vincoming (line-to-line)
--
Voltage across contacts, Vdiff
Vdiff = √(V₁² + V₂² − 2·V₁·V₂·cosδ)
--
Vdiff per-unit on system base
--
Vdiff as % of nominal
--
Peak voltage across contacts
Vpeak = Vdiff × √2
--
Current Analysis
Steady-state current, Iss
Iss = Vdiff / (√3 × Xtotal,Ω)
--
Peak asymmetric current, Ipeak
Ipeak = Iss × √2 × (1 + e−π/(X/R))
--
Asymmetry multiplier (Kpeak)
--
Rated system fault current
Ifault = Sbase / (√3 × Vbase × Xtotal,pu)
--
Ipeak as multiple of rated
--
Energy and Power
Instantaneous 3-phase power
P = Vdiff² / Xtotal,Ω
--
Energy during closure transient
E = P × tclosing
--
Equivalent fault MVA
S = Vdiff,pu² / Xtotal,pu × Sbase
--
Equivalent % of bolted 3-phase fault
--
3
Angle Sweep Chart
Key parameters vs. phase angle (0° to 180°)
Voltage across contacts (kV)
Peak transient current (kA)
Transient energy (MJ)
Sync check window (±10°)
Current operating point
4
Reference Tables
Standard values for design and relay setting verificationQuick Reference — Voltage Across Contacts (Equal Magnitudes)
| Phase Angle | Vdiff (pu) | Vdiff (% nom) | Risk Level |
|---|---|---|---|
| 0° | 0.000 | 0.0% | None |
| 5° | 0.087 | 8.7% | Minimal |
| 10° | 0.174 | 17.4% | Low |
| 20° | 0.347 | 34.7% | Moderate |
| 30° | 0.518 | 51.8% | Significant |
| 45° | 0.765 | 76.5% | High |
| 60° | 1.000 | 100.0% | Very High |
| 90° | 1.414 | 141.4% | Severe |
| 120° | 1.732 | 173.2% | Extreme |
| 150° | 1.932 | 193.2% | Catastrophic |
| 180° | 2.000 | 200.0% | Maximum |
Typical Sync Check Relay Settings by Application
| Application | Angle Window | Voltage Diff | Slip Freq |
|---|---|---|---|
| Generator synchronizing | ±10° | ≤5% | ≤0.067 Hz |
| Transmission tie line | ±20° | ≤5% | ≤0.05 Hz |
| Distribution feeder | ±15° | ≤10% | ≤0.1 Hz |
| Emergency / black start | ±30° | ≤10% | ≤0.1 Hz |