Instructions
- Read each scenario carefully, observing the instrument readings and mini-synchroscope animation.
- Select the best course of action from the choices provided, then click Check Answer.
- After answering, expand the engineering analysis for a detailed explanation.
- Complete all 8 scenarios to receive your performance assessment.
- Scenarios progress from basic (green) to intermediate (yellow) to advanced (red).
Situation
Instrument Readings
Synchroscope
What should you do?
Correct Action
Close the breaker as the needle approaches 12 o'clock. These are ideal synchronization conditions.
Analysis
Slip frequency = 0.067 Hz, meaning the phase angle changes at approximately 24°/sec. With a typical 5-cycle breaker (83 ms closing time), the angle changes only about 2° during closing — well within acceptable limits.
Voltage difference is 0.4 kV out of 138 kV (0.3%), far below the typical 5% limit. This small mismatch will cause negligible reactive power exchange upon closing.
Situation
Instrument Readings
Synchroscope
What should you do?
Correct Action
Do NOT close. The slip frequency (0.33 Hz) far exceeds the typical acceptable limit of 0.067–0.1 Hz. Request frequency adjustment.
Analysis
At 0.33 Hz slip, the phase angle is changing at approximately 120°/sec. With a 5-cycle breaker closing time (~83 ms), the angle changes by about 10° during the closing operation. Combined with human reaction time (~200 ms), the total angular uncertainty is approximately 34° — far too high for a safe closure.
Even if you timed the closure perfectly at 12 o'clock, the rapid rate of angle change means that any small timing error results in a large angular mismatch at the instant of contact. At 138 kV, each degree of mismatch produces roughly 2.4 kV across the breaker contacts.
Situation
Instrument Readings
Synchroscope
What should you do?
Correct Action
Do not close yet. Request frequency adjustment so the incoming source rotates clockwise (incoming slightly faster than bus).
Analysis
Counter-clockwise rotation indicates the incoming source frequency is slightly lower than the bus frequency. While it is technically possible to close at 12 o'clock during a CCW rotation, best practice strongly favors clockwise rotation for several reasons:
1. When the incoming generator is slightly faster (CW), it immediately picks up real power load upon closing, which is the normal desired operating condition.
2. With CCW rotation (incoming slower), the generator initially acts as a motor, absorbing power from the system. The governor must then respond to increase fuel/steam, which creates a transient operating condition.
3. Timing is more intuitive with CW rotation — the operator can anticipate the needle reaching 12 o'clock and account for breaker closing time.
Situation
Instrument Readings
Synchroscope
What should you do?
Correct Action
Do NOT close. Request excitation adjustment on the incoming generator to reduce the voltage difference to within 5% (preferably 0–2%) before synchronizing.
Analysis
A synchroscope only indicates the phase angle difference and slip frequency between two sources. It does NOT indicate voltage magnitude difference. The synchroscope can show "perfect" conditions while voltage mismatch is dangerously high.
An 8.5% voltage difference (11.5 kV at 138 kV) will cause a large reactive power (MVAR) surge at the moment of closing. The lower-voltage source (incoming unit) will immediately absorb a large amount of reactive power from the system. This can:
• Cause voltage regulation problems across the system
• Overload generator excitation systems
• Stress transformer windings and insulation
• Trip protective relays (loss-of-field, over-excitation)
Situation
Instrument Readings
Synchroscope
What should you do?
Correct Action
This is a dead bus closure. Verify the bus is dead, all grounds are removed, and the switching order is complete, then close the breaker. No synchronization required.
Analysis
Dead bus closing is fundamentally different from synchronizing two live sources. With no voltage on the receiving bus, there is no opposing voltage source and therefore no risk of out-of-phase closure. The synchroscope cannot function without voltage on both sides — it is not malfunctioning, it simply has no signal.
The key safety concerns for dead bus closing are entirely different from synchronization:
• Confirm the bus is truly de-energized (use approved voltage indicators/detectors)
• Verify all protective grounds have been removed
• Confirm the switching order authorizes the closure
• Ensure downstream loads and equipment are ready for energization
• Be aware of cold load pickup (inrush) if loads are connected
Situation
Instrument Readings
Synchroscope
What should you do?
Correct Action
ABSOLUTELY DO NOT CLOSE. 180° is the worst possible phase angle for synchronization. This closure would be catastrophic.
Analysis
At 180° phase difference, the voltage across the breaker contacts equals the sum of both source voltages:
V_across = V_bus + V_incoming = 347.0 + 346.5 = 693.5 kV
This is approximately twice the rated voltage appearing across the breaker contacts at the instant of closing. The resulting transient current would be:
• Potentially exceeding the breaker's rated short-circuit interrupting capability
• Limited only by the system impedance and source impedances
• Producing enormous electromagnetic forces on bus conductors and equipment
Physical consequences of a 180° closure at 345 kV:
• Generator shaft torsional failure (shaft can physically twist and break)
• Transformer winding deformation and insulation failure
• Bus structure physical damage from electromagnetic forces
• Fire and explosion risk at the breaker
• System-wide cascading failures from the resulting disturbance
• Potential injury or death to personnel in the substation
Situation
Instrument Readings
Synchroscope
What should you do?
Correct Action
STOP and investigate. Never trust a single instrument, especially one that may be malfunctioning. Do not close until the synchroscope condition is resolved.
Analysis
A synchroscope needle that is completely stationary while both sides are energized has several possible causes, each with different implications:
1. Instrument failure (mechanical): The synchroscope motor or needle mechanism is broken. The displayed angle has no meaning. Closing could be at any actual angle.
2. Blown fuse or open circuit: One of the PT circuits feeding the synchroscope has lost its signal. The instrument is not receiving proper input. The displayed angle is meaningless.
3. PT wiring error: The synchroscope may be connected to incorrect phases, or a phase reversal may exist. The displayed angle could be offset by 120° or 240° from the true angle.
4. Frequencies truly identical: It is theoretically possible that both sources are at exactly the same frequency with a fixed 60° phase offset. However, maintaining exactly identical frequencies for any sustained period is extremely unlikely on a real power system. Slight governor variations continuously adjust frequency.
If the needle is truly stuck at 60° and this represents the actual phase angle, closing would apply approximately:
V_across = 2 x 138.25 x sin(30°) = 138.25 kV across the breaker contacts — essentially full line-to-ground voltage. This is unacceptable.
Situation
Instrument Readings
Synchroscope
What should you do?
Correct Action
Communicate conditions to the dispatcher. If authorized for emergency closing with widened parameters, carefully time the closure at 12 o'clock during a stable window. The emergency does not override physics.
Analysis
Island reconnection is one of the most challenging synchronization operations a field operator can face. The conditions here are not ideal but may be acceptable for an emergency operation:
Voltage difference (4.3%): Within the typical 5% limit, but on the high side. The reactive power surge upon closing will be significant but manageable.
Slip frequency (0.125 Hz): Above the normal 0.067 Hz limit but below the absolute maximum typically used in emergencies (0.2 Hz). Phase angle changes at ~45°/sec, giving about 3.7° change during a 5-cycle breaker close — still acceptable.
Fluctuating conditions: This is the most concerning factor. Varying voltage and frequency mean the needle speed and position are unpredictable. The operator must watch for a "window" of relatively stable conditions.
Why not refuse entirely (option B)? While conditions are non-ideal, an islanded system will continue to degrade over time. Frequency may diverge further, voltage collapse may occur, or generators may trip. Delaying indefinitely could make reconnection impossible.
Why not close immediately (option A)? Rushing without proper assessment and communication is never acceptable, even in emergencies. A bad closure creates a second emergency.
Performance Assessment
Complete all 8 scenarios to see your performance assessment.